What is EICR Testing? UK 2026 Guide | C-Lec Electrical
EICR Help • C-Lec Electrical

What is
EICR Testing

EICR testing is the practical electrical examination of a property's fixed wiring. Combines visual inspection with electrical measurements: insulation resistance, continuity, polarity, RCD trip times and earth fault loop impedance. Conducted per IET Wiring Regulations BS 7671. Identifies safety defects and confirms the installation meets UK standards. Takes 2-4 hours typical for 3-bedroom property.

Updated: April 2026
Unit rate: 24.7p/kWh (Ofgem Q2 2026)
Coverage: Bedford · Milton Keynes · Northampton
The short answer

EICR testing is the technical examination phase of an Electrical Installation Condition Report. It combines two parts: visual inspection and electrical testing. Visual inspection involves the registered electrician examining consumer unit, sockets, switches, light fittings and visible cabling for damage, wear or non-compliance with current standards. Electrical testing involves taking measurements on each circuit using specialised test equipment: insulation resistance test (measures insulation between live conductors and earth, must be over 1 megohm), continuity test (confirms earth and ring main paths are unbroken), polarity test (confirms live and neutral are correctly wired), RCD trip time test (confirms residual current devices trip within required time), earth fault loop impedance test (measures resistance of fault path for safety calculations). Each circuit is tested individually with results recorded in tabular form on the EICR document. Conducted per IET Wiring Regulations BS 7671. Takes 2-4 hours typical for a UK 3-bedroom property.

By the numbers

The figures that matter

Visual+ electrical

Two parts

EICR testing combines visual inspection and electrical measurement testing of each circuit.

5key tests

Measurements

Insulation resistance, continuity, polarity, RCD trip time, earth fault loop impedance per circuit.

BS 7671standard

UK Wiring Regs

All EICR testing conducted per IET Wiring Regulations BS 7671 18th Edition. UK national standard.

2-4hours

Duration

Typical UK 3-bedroom property EICR testing takes 2-4 hours including all visual and electrical tests.

Where to start

Four things to consider

Visual inspection first

Electrician examines consumer unit, sockets, switches, light fittings, visible cabling for damage or non-compliance.

Electrical testing

Insulation resistance, continuity, polarity, RCD trip times, earth fault loop impedance measured per circuit.

Specialised equipment

Test equipment includes multifunction tester, insulation tester, RCD tester, loop impedance meter.

BS 7671 standard

All testing follows IET Wiring Regulations BS 7671 18th Edition. UK national standard for installations.

The detailed answer

What EICR testing actually involves and why each test matters

EICR testing is more than just a visual look at the consumer unit. It involves systematic electrical measurements that verify safety in ways human eyes cannot detect. Understanding what's tested helps you appreciate the value of EICRs and why proper testing takes 2-4 hours.

Part 1: Visual inspection.

  • Examine consumer unit (fuse board) for: type, age, RCD protection, condition, accessibility, labelling.
  • Check sockets and switches for: damage, scorching, looseness, age.
  • Inspect light fittings and switches for: damage, missing parts, modifications.
  • Examine visible cabling for: damage, wear, correct routing, support clips.
  • Check earthing arrangements: main bonding to gas/water, supplementary bonding in bathrooms.
  • Inspect for any non-compliant additions or modifications.
  • Look at protective devices (fuses, MCBs, RCDs) for correct type and rating.
  • Typically takes 30-60 minutes for a 3-bedroom property.

Part 2: Test 1 - Insulation resistance test.

  • What it measures. Insulation resistance between live conductors and earth, plus between live conductors themselves.
  • Why it matters. Damaged or degraded insulation can cause electric shock, fire or unreliable circuit operation.
  • How it works. Specialised insulation tester applies 250V or 500V DC to circuit. Measures current leakage through insulation.
  • BS 7671 requirement. Insulation resistance must be greater than 1 megohm.
  • Typical good reading. Hundreds of megohms or 'OL' (over limit) on tester.
  • Failures. Damaged cable insulation, water ingress, deteriorated old wiring.
  • Per circuit. Each circuit tested separately with all loads disconnected.

Part 2: Test 2 - Continuity test.

  • What it measures. Earth conductor continuity throughout circuit. Ring main continuity for socket circuits.
  • Why it matters. Broken earth means no protection from earth faults. Unsafe.
  • How it works. Tester sends low current through earth path. Measures resistance.
  • BS 7671 requirement. Earth continuity should be very low resistance (typically less than 1 ohm).
  • Ring main continuity. Specifically for socket ring circuits. Confirms ring is intact.
  • Per circuit. Each circuit's earth path tested.
  • Common issues. Damaged earth wire, poor terminations, broken ring at junction.

Part 2: Test 3 - Polarity test.

  • What it measures. Confirms live and neutral conductors are correctly identified at each accessory.
  • Why it matters. Reversed polarity means switches break neutral instead of live. Switching off doesn't isolate fault. Lamps stay live.
  • How it works. Tester confirms live conductor reaches the live terminal at sockets and switches.
  • BS 7671 requirement. All accessories must have correct polarity.
  • Common issues. Reversed wiring at sockets, particularly older installations or DIY work.
  • Per accessory. Each socket and switch checked.

Part 2: Test 4 - RCD trip time test.

  • What it measures. Time RCD takes to trip when fault current flows.
  • Why it matters. RCDs save lives by tripping quickly during earth faults. Slow or non-tripping RCD is dangerous.
  • How it works. RCD tester injects controlled fault current at multiple test currents (e.g. 1x, 5x rated trip).
  • BS 7671 requirement. 30mA RCD must trip within 40ms at 5x rated current. Within 300ms at rated current.
  • Common issues. RCD failed (mechanical failure), wrong type for application, missing on circuits requiring it (showers, outdoor).
  • Per RCD. Each RCD tested individually.

Part 2: Test 5 - Earth fault loop impedance.

  • What it measures. Total resistance of earth fault path from circuit to substation and back.
  • Why it matters. Determines fault current and whether protective devices will operate within safe time.
  • How it works. Loop impedance tester measures path including supply transformer, neutral, earth.
  • BS 7671 requirement. Specific maximum values per circuit type and protective device.
  • Common issues. Long cable runs, undersized cables, poor earthing arrangements.
  • Per circuit. Calculated for each circuit type.

Test equipment used:

  • Multifunction tester (MFT). Combines insulation, continuity, loop impedance, RCD testing in one unit. Common UK brands: Megger, Fluke, Kewtech, Metrel.
  • Approved voltage indicator. Confirms circuits are dead before testing. Two-pole tester typical.
  • Proving unit. Verifies voltage indicator works correctly.
  • Calibrated to UK standards. All test equipment annually calibrated and certified.
  • Cost of equipment. Professional MFT £300-£1500. Annual calibration £50-£150.

What's documented during testing:

  • Each test result recorded on EICR document.
  • Tabular format with circuit name, test type, measured value, pass/fail.
  • Defects noted with C1, C2, C3 or FI codes.
  • Visual observations recorded.
  • Limitations of testing (anything not fully tested).
  • Overall result: Satisfactory or Unsatisfactory.
  • Recommendations for any required action.

Power requirements during testing:

  • Power must be off for insulation resistance test (could damage equipment).
  • Power on for RCD and loop impedance tests.
  • Each circuit tested individually, briefly powered off then on.
  • Total power-off time 30-60 minutes spread across visit.
  • Some whole-property power-off briefly (15-30 minutes).
  • Disconnect sensitive equipment beforehand if concerned.

Why some tests reveal issues that visual inspection misses:

  • Insulation degradation invisible until tested.
  • Internal cable damage hidden by outer sheath.
  • Reversed polarity not visible without testing.
  • RCD mechanical failure can occur without external signs.
  • Earth path interruptions can be intermittent.
  • Loop impedance issues only revealed through measurement.
  • This is why EICR testing is more thorough than just visual checks.

Common UK EICR test failures:

  • Old installations. Insulation resistance failure in pre-1970s rubber-insulated cables.
  • Bathroom modifications. Missing or insufficient bonding.
  • Outdoor lights. Damaged cables and lack of RCD protection.
  • Kitchen rewires. Polarity errors at sockets.
  • Older fuse boards. No RCD protection (typically C3 not C2).
  • DIY additions. Various issues from unqualified work.
  • Garage and outbuilding installations. Insulation degradation from moisture.

What you can do to prepare for EICR testing:

  • Provide access to consumer unit (clear any storage).
  • Provide access to all sockets and switches.
  • Inform of any specific concerns or recent issues.
  • Provide previous EICR if available.
  • Plan for power-off periods (save work, defrost food, etc).
  • Be present or available for questions.
  • Allow 2-4 hours for typical 3-bedroom property.
UK source check. EICR testing procedures documented in IET Wiring Regulations BS 7671 18th Edition published by Institution of Engineering and Technology (theiet.org). Specific test methods detailed in IET On-Site Guide and Inspection and Testing Guide. Test requirements: insulation resistance >1 megohm, RCD trip time <40ms at 5x rated current, earth fault loop impedance per circuit type tables. Test equipment from UK manufacturers: Megger, Fluke, Kewtech, Metrel. Annual calibration required for accuracy. Registered electricians: NICEIC, NAPIT, ELECSA, STROMA. Required for UK rental properties under Electrical Safety Standards 2020. Always check current IET guidance.
Cost breakdown

Real number ranges

EICR testing costs (UK 2026)

Domestic testing (1-3 bed) 150 to 300 £
Larger property testing (4+ bed) 250 to 500 £
Commercial testing 300 to 1000 £
Step by step

EICR testing process

01
30-60min

Visual inspection

Examine consumer unit, sockets, switches, light fittings, visible cabling for damage or non-compliance.

02
60-90min

Electrical tests

Insulation resistance, continuity, polarity, RCD trip times, earth fault loop impedance per circuit.

03
15-30min

RCD specifics

Test residual current device trip times. Confirms protection meets BS 7671 standards.

04
30-60min

Document findings

Record all test results on EICR document. Code defects C1, C2, C3 or FI. Determine overall outcome.

Practical guidance

Four EICR testing essentials

Visual plus electrical

EICR testing combines visual inspection and electrical measurements. Both essential for full safety assessment.

Five key electrical tests

Insulation resistance, continuity, polarity, RCD trip times, earth fault loop impedance per circuit.

Specialised equipment needed

Multifunction tester (MFT), approved voltage indicator and proving unit. Calibrated annually.

BS 7671 standard

All testing per IET Wiring Regulations BS 7671 18th Edition. UK national standard for electrical installations.

Side by side

Compare the options

Visual inspection only

Visual inspection only

  • 30-60 minutes. Quicker.
  • Identifies obvious issues. Damaged sockets, scorching.
  • Misses insulation degradation. Hidden defects.
  • Cannot test RCD function.
  • NOT a valid EICR alone.
Full EICR testing

Full EICR testing

  • 2-4 hours. Thorough assessment.
  • Visual plus electrical tests.
  • Detects hidden defects. Insulation, polarity, RCD failures.
  • Tests RCD trip times. Confirms safety.
  • Valid EICR per BS 7671.

Knowing what EICR testing involves helps UK property owners understand the value of a thorough inspection. Our full EICR Help hub covers EICR cost, validity periods, legal requirements and broader electrical inspection guidance for UK homes and businesses.

Part of the hub

Visit the EICR Help Hub

This article is one chapter inside our complete EICR Help knowledge base. The hub covers EICR cost, validity periods, legal requirements plus broader electrical inspection guidance for UK homes.

Keep reading

More on smart home

Three further EICR articles in the same hub group cover related questions. The first is what is eicr for the broader definition. The second covers how long does an eicr take for duration. The third is what is an eicr report for the document.

Frequently asked

What is EICR Testing FAQ

What is EICR testing?
EICR testing is the practical electrical examination of a property's fixed wiring during an Electrical Installation Condition Report. Combines visual inspection (consumer unit, sockets, switches, cabling) with electrical measurements: insulation resistance, continuity, polarity, RCD trip times, earth fault loop impedance. Conducted per IET Wiring Regulations BS 7671. Takes 2-4 hours typical for 3-bedroom property.
What tests are done in EICR?
Five key electrical tests plus visual inspection. 1) Insulation resistance (between live and earth, must be >1 megohm). 2) Continuity (earth and ring main paths). 3) Polarity (live and neutral correctly wired). 4) RCD trip time (must trip within 40ms at 5x rated current). 5) Earth fault loop impedance (resistance of fault path). Each circuit tested separately with results recorded.
How is EICR testing different from PAT testing?
EICR tests fixed wiring (consumer unit, circuits, sockets in walls, light fittings). PAT (Portable Appliance Testing) tests plug-in appliances like kettles, computers, lamps. Different equipment, different procedures, different certificates. Both important for electrical safety but distinct services. Most UK properties need both: EICR every 5 years (rentals) plus PAT annually (commercial usually) for portable equipment.
What equipment is used for EICR testing?
Specialised electrical test equipment. Multifunction tester (MFT) combines insulation, continuity, loop impedance, RCD testing in one unit (£300-£1500). Common UK brands: Megger, Fluke, Kewtech, Metrel. Plus approved voltage indicator and proving unit. All equipment annually calibrated to UK standards. Registered electricians (NICEIC, NAPIT, ELECSA, STROMA) maintain calibration certificates.
Why does EICR testing need power off?
Insulation resistance test applies 500V DC to the circuit. Power must be OFF and loads disconnected to avoid damaging equipment and ensure accurate readings. Other tests (RCD, loop impedance) need power ON. Each circuit tested with power off briefly (5-10 minutes) then on for other tests. Total power-off time 30-60 minutes spread across visit. Save work, plan for fridges and freezers staying closed.