What is Bonding in Electrical Systems? | C-Lec Electrical
Consumer unit guide • Milton Keynes

What is Bonding
in Electrical Systems?

UK bonding explained. The difference between main protective bonding plus supplementary bonding, what BS 7671 requires plus where each conductor is fitted in 2026.

Updated: April 2026
Written by: Curtis Williams, Director, C-Lec Electrical
For: Milton Keynes & Bedfordshire homeowners
The short answer

Bonding is the practice of connecting metallic parts that are not part of the electrical installation (gas pipes, water pipes, structural metalwork) to the earthing system using dedicated conductors. The goal is to keep all metalwork in the property at the same electrical potential during a fault so that nobody touching two metal items at once gets a shock. UK bonding splits into main protective bonding (the gas plus water bonds at the MET, BS 7671 411.3.1.2) plus supplementary bonding (used in specific locations like older bathrooms, BS 7671 415.2). The two have different cable sizes, different rules plus different test requirements.

The numbers behind it

Three figures
worth knowing

10mm²

Main Bonding

The standard CSA for main protective bonding to gas plus water on a UK domestic install with a TN-C-S supply.

4mm²

Supplementary Bonding

Typical CSA for supplementary bonding conductors. Mechanical protection (clipped or in conduit) reduces the requirement to 2.5mm sq.

411

BS 7671 Section

Section 411.3.1.2 covers main protective bonding. Section 415.2 covers supplementary bonding for additional protection.

Two distinct types

Main bonding plus
supplementary bonding

Both types share a common goal of keeping metalwork at equal potential. The where, when plus how differ significantly between them.

01

Main Protective Bonding

BS 7671 Section 411.3.1.2

What it is. A dedicated conductor running from the Main Earthing Terminal to each "extraneous-conductive-part" entering the building. The classic targets are the incoming gas service pipe plus the incoming water service pipe. Where structural metalwork (steel beams, oil tank piping, lightning protection downconductors) is exposed plus accessible, it must also be bonded.

Why it exists. Without main bonding the metallic services would float at an indeterminate potential during a fault. A person touching the gas tap plus the kitchen sink simultaneously could feel a shock voltage. Main bonding ties everything to the same reference at the MET so that even during a fault every metal object in the property sits at the same potential as every other.

Where it terminates. One end at the MET via a bolted connection. The other end on the gas or water pipe via a BS 951 earthing clamp within 600mm of the gas meter or stop tap, on the customer side of any insulating section.

Typical CSA10mm sq
Clamp standardBS 951
WhereMET to service entry
02

Supplementary Bonding

BS 7671 Section 415.2

What it is. Additional bonding conductors connecting metallic parts within a specific location (typically a bathroom or shower room) to each other plus to the CPC of any circuit serving that location. Common targets include taps, radiator pipes, structural steel that enters the room plus any exposed earth-bonded metalwork.

When it is needed. Required by 415.2 only where one of two conditions applies: (1) automatic disconnection of supply cannot be achieved within the BS 7671 disconnection times for the circuits serving the location; (2) all final circuits do not have 30mA RCD protection. On modern UK installs where every circuit is RCD or RCBO protected, supplementary bonding is normally not required for new bathrooms. Older bathrooms wired before RCD protection was universal almost always needed it.

Where it terminates. Each end on a metallic part within the location. The conductor itself is normally clipped or run in conduit for mechanical protection. No separate clamp standard required because it is not part of the main earthing system.

Typical CSA2.5 to 4mm sq
Section415.2
WhereWithin bathroom or shower room
The detailed answer

Equal potential is the safety goal

The whole rationale for bonding sits on a simple physics principle. An electric shock requires a potential difference. If two metal objects touched simultaneously by the same person are at the same voltage, no current flows through that person regardless of how high the voltage is above earth. Bonding works by deliberately tying metalwork together so any rise in potential affects every metal item equally.

The earth fault scenario

To see why bonding matters, picture an earth fault inside an appliance. A live conductor inside a washing machine has worn through its insulation plus is now touching the metal casing. The casing is connected to earth via the CPC (the green-yellow wire) which runs back to the consumer unit plus eventually to the MET. Earth fault current flows through that path. The MCB upstream detects the overcurrent plus trips. So far so good.

Now consider what happens during the few milliseconds before the MCB trips. The earth fault loop has some impedance which means there is a voltage drop along it. The MET sits at a slightly elevated potential above true earth. Anything connected to the MET (the consumer unit casing, the earth bar, every CPC in the property) shares that elevated potential.

The metallic gas pipe in the kitchen is not connected to the electrical installation. Without main bonding it sits at true earth potential. A person touching the washing machine casing plus the gas tap at the same moment briefly bridges the voltage difference between the two. With main bonding the gas pipe shares the elevated potential of the MET. The voltage difference disappears. The shock disappears with it.

Why supplementary bonding rules have changed

Older UK installs (pre-17th Edition) could not always rely on RCD protection. The fault disconnection time on a TN-C-S system without an RCD depends on the earth fault loop impedance which is harder to control in a wet environment like a bathroom. The historic answer was supplementary bonding within the room itself. By tying the taps, pipes, radiators plus light fittings together, the room became its own equipotential zone. Even if disconnection was slow, no significant voltage difference existed within reach of a wet person.

The 17th Edition (2008) made 30mA RCD protection mandatory on bathroom circuits. Once an RCD is present, disconnection happens within 40ms which is fast enough to prevent dangerous shock without the equipotential zone. BS 7671 415.2 now states supplementary bonding can be omitted where:

  • All low voltage circuits in the location have automatic disconnection of supply meeting the times in Table 41.1.
  • All low voltage circuits in the location have additional protection by a 30mA RCD.
  • All extraneous-conductive-parts within the location are effectively connected to the main protective bonding.

On modern UK domestic installs all three conditions are normally met. Supplementary bonding in new bathrooms is therefore typically not required. Older bathrooms still have it from the original install. EICR engineers normally leave existing supplementary bonding in place because removal serves no benefit plus risks creating non-compliance.

Cable sizing fundamentals

BS 7671 Section 544 sets the cross-sectional areas for protective bonding:

  • Main bonding for TN-S: half the CSA of the main earthing conductor with a minimum of 6mm sq plus a maximum of 25mm sq.
  • Main bonding for TN-C-S (PME): based on the supply neutral CSA. Typically 10mm sq for a 25mm sq supply tail (the standard UK domestic case).
  • Supplementary bonding: a function of the connected CPCs. Typically 2.5mm sq if mechanically protected, 4mm sq if not.
UK regulatory source check. The standards referenced here come from BS 7671:2018+A2:2022 Sections 411.3.1.2 (main bonding), 415.2 (supplementary bonding) plus 544 (cross-sectional areas) plus BS 951 (earthing clamps) published by BSI plus the IET. C-Lec Electrical is a registered installer covering Milton Keynes, Bedford plus the surrounding Bedfordshire area.
Where you'll find them

Five common locations
where bonding lives

Bonding conductors are normally tucked out of sight but follow predictable routes around UK domestic properties. These are the five most common locations.

Main bonding
Gas meter

A green-yellow conductor terminating on the incoming gas pipe via a BS 951 clamp. Within 600mm of the gas meter on the customer side. Travels back to the MET in conduit, capping or clipped along skirting. Always present on UK gas-supplied properties.

Main bonding
Water stop tap

A green-yellow conductor on the incoming water pipe via a BS 951 clamp. Within 600mm of the stop tap. Modern UK supplies often use plastic pipe at the entry which removes the bond requirement. Where copper or steel enters the building bonding is mandatory.

Main bonding
Structural steel

Where exposed accessible structural metalwork is present (steel beams in renovations, lightning protection downconductors on heritage buildings, external oil tank pipework) main bonding is required. Less common on standard UK domestic builds. Always required where present.

Supplementary
Older bathroom

A network of green-yellow conductors interconnecting taps, radiator pipes, exposed structural metal plus light fittings inside an older bathroom. Pre-2008 standard. Normally left in place during modern upgrades. Removal serves no benefit plus risks creating non-compliance.

Termination point
The MET

The MET is where every main bonding conductor terminates. Inside the consumer unit on most modern installs or in the meter cabinet on older configurations. Look for the converging green-yellow conductors plus the SAFETY ELECTRICAL CONNECTION DO NOT REMOVE label.

Practical takeaways

Four things every homeowner
should know

Bonding is not earthing

Bonding ties metalwork to the earthing system. The earthing system itself is a separate concept that returns fault current to the supply.

Old main bonding often needs upgrading

Pre-2008 main bonding was sometimes 6mm sq. BS 7671 now requires 10mm sq on a UK domestic TN-C-S supply. Discovered routinely during board upgrades.

Plastic pipe removes the gas bond?

Only the section that is plastic. If the gas pipe is metal at the meter even on a plastic-supply property bonding is still required. Always check.

Existing bathroom bonds stay put

Modern bathrooms with full RCD protection do not need supplementary bonding. Existing bonds in older bathrooms should be left in place.

Bonding work needed?

Earthing plus Bonding Upgrades in Milton Keynes

C-Lec Electrical inspects, replaces plus certifies main protective bonding to BS 7671 across Milton Keynes, Bedford plus the surrounding Bedfordshire area. Full EIC plus Building Control notification on completion.

For the wider context on consumer units, RCBOs, AFDDs plus the regulations behind UK distribution boards, head back to our full guide to consumer units where every common question is answered in one place.

Part of the hub

Back to the Consumer Units Guide

This article sits inside our complete Consumer Units knowledge base. The hub covers everything from board types plus RCBOs through to landlord requirements plus BS 7671 wiring regulations.

Keep reading

More on consumer
unit anatomy

To understand the central earthing point that every main bonding conductor terminates at, head to what is the main earthing terminal for the practical breakdown of MET configurations plus cable sizes. To understand the BS 7671 framework around earthing plus bonding, see consumer unit wiring regulations. To understand how RCDs interact with bonding requirements (especially in bathrooms), see are RCDs legally required. If you need bonding work or a board upgrade in Milton Keynes or Bedford, our consumer unit upgrades service page is the fastest route to a quote.

Frequently asked

Bonding questions

Do I still need bonding if my gas plus water supplies use plastic pipes?
Possibly not. The bonding requirement applies to extraneous-conductive-parts. A fully plastic gas or water service pipe is not conductive so it cannot become live during a fault plus does not need bonding. However many UK properties have a plastic supply that converts to copper or steel inside the building. The bond is required wherever metal pipework is present plus accessible. An EICR engineer or registered electrician will check at the point of entry plus document whether bonding is required.
Why was my old bathroom full of green-yellow wires plus the new one has none?
Older bathrooms wired before the 17th Edition of BS 7671 normally required supplementary bonding to create a local equipotential zone because RCD protection was not universal. Modern bathrooms protected by 30mA RCDs (or RCBOs) on every circuit normally do not need supplementary bonding because BS 7671 415.2 permits omission where all the conditions are met. Both layouts are compliant under their respective rules. The change reflects the evolution of the protective device technology not a change in the underlying physics.
Can I disconnect old supplementary bonds to tidy up my bathroom?
No. Even if your modern install meets the conditions of 415.2 for omission, removing existing supplementary bonds risks creating a non-compliance during the next EICR plus serves no practical benefit. Existing bonds remain compliant by default. Any work to remove them is notifiable under Part P plus must be carried out by a registered electrician who can certify the resulting installation still meets BS 7671. The cost of leaving them in place is zero. The cost of removing them is real with no upside.
How do I tell if my main bonding is the right size?
Look at the green-yellow conductor running from the MET to the gas plus water clamps. The cable will normally have its CSA marked along the length: 6mm, 10mm, 16mm. For a UK domestic install on a TN-C-S (PME) supply with a standard 25mm sq supply tail, the main bonding should be 10mm sq. If it shows 6mm sq it pre-dates current standards plus will need upgrading at the next consumer unit replacement. An EICR engineer will measure plus document the actual CSA during inspection.
Is bonding work notifiable under Part P?
Replacement or addition of main protective bonding is notifiable under Part P of the Building Regulations because it is part of the fixed wiring of the property. The work must be carried out by a registered electrician (NICEIC, NAPIT, Stroma or ELECSA) who can issue an EIC plus a Building Control notice. Routine inspection plus testing of existing bonding during an EICR is not notifiable but the EICR itself documents whether the bonding is satisfactory or needs remedial work.