What is the Main Earthing Terminal? | C-Lec Electrical
Consumer unit guide • Milton Keynes

What is the Main
Earthing Terminal?

The MET is the central earthing point of every UK installation. What it does, what physically terminates there, what cable sizes BS 7671 demands plus how to identify yours during an upgrade.

Updated: April 2026
Written by: Curtis Williams, Director, C-Lec Electrical
For: Milton Keynes & Bedfordshire homeowners
The short answer

The Main Earthing Terminal (MET) is a copper bar or terminal block that acts as the single earthing point of your installation. Every protective conductor in the property terminates there. The earth from the supply (or from a local earth electrode) connects on one side; every CPC from the consumer unit, every main protective bonding conductor plus any supplementary bonds connect on the other. Without a sound MET no protective device on your consumer unit can do its job. BS 7671 specifies 16mm sq minimum for the main earthing conductor on most UK domestic installs.

The numbers behind it

Three figures
worth knowing

16mm²

Main Earthing Conductor

Minimum CSA for the main earthing conductor on a UK domestic install with TN-C-S supply. Larger installs require 25mm sq or above.

543

BS 7671 Section

Section 543 sets the cross-sectional area requirements for protective conductors based on the line conductor or earth fault current.

951

BS Standard

BS 951 defines the earthing clamp standard. Copper construction, marked SAFETY ELECTRICAL CONNECTION DO NOT REMOVE.

What connects to it

Five conductors
terminate at the MET

The MET is the meeting point of every protective conductor in your installation. Five distinct conductor types arrive there.

01

The earth from the supply

For TN-S plus TN-C-S systems, the earth conductor from the DNO arrives at the MET. TN-S uses the supply cable's metallic sheath. TN-C-S (PME) uses a combined earth-neutral conductor split locally to provide an earth connection on a dedicated terminal.

Typical CSA 16mm sq
02

The earth electrode (TT only)

On a TT system there is no earth from the supply. The installation has its own earth rod driven into the ground outside the property. The conductor from the rod terminates at the MET via a BS 951 earthing clamp.

Typical CSA 16mm sq
03

CPCs from the consumer unit

Every circuit's circuit protective conductor (CPC) terminates on the MET via the consumer unit earth bar. This is the path that carries earth fault current from any appliance fault back to the supply earth.

Typical CSA 1.5 to 6mm sq
04

Main bonding to gas plus water services

Main protective bonding conductors run from the MET to the incoming gas pipe plus the incoming water pipe (within 600mm of the meter or stop tap). This brings the metallic services to the same earth potential as the installation.

Typical CSA 10mm sq
05

Main bonding to structural metalwork

Where structural metalwork (steel beams, lightning protection downconductors, oil tank pipework) is exposed plus accessible, it must also be bonded to the MET. Less common in standard UK domestic builds. Always required where present.

Typical CSA 10mm sq
The detailed answer

The single point that holds the whole earthing system together

UK domestic earthing exists for one purpose: to provide a low-impedance return path for fault current so that the protective devices upstream can detect the fault plus disconnect the supply within the BS 7671 disconnection times. Without that return path an MCB cannot trip on an earth fault. An RCD has nothing to compare its line plus neutral currents against. The whole automatic disconnection of supply (ADS) framework collapses.

The MET is the single physical point that ties the whole system together. Every protective conductor in the installation either originates from or terminates at the MET. Three things follow from that:

  • The MET must be physically robust. A copper bar with bolted connections, normally rated to handle the prospective fault current of the supply for the disconnection time without overheating.
  • The MET must be accessible plus identifiable for testing. EICR engineers measure the resistance from the MET to every accessible earth point during inspection.
  • The MET must be permanent plus labelled. BS 7671 requires the durable label "SAFETY ELECTRICAL CONNECTION DO NOT REMOVE" near the terminal so that it is not accidentally disturbed.

Where the MET physically lives

On most UK domestic installs the MET is one of three physical configurations:

  • Inside the consumer unit. The earth bar at the base of the consumer unit doubles as the MET on most modern installs. The supply earth, all CPCs plus the main bonding conductors all terminate on this bar.
  • Adjacent to the consumer unit. A separate copper bar mounted in the same enclosure or on the same backboard, fed by the supply earth plus connected to the consumer unit earth bar via a short link.
  • At the meter cabinet. On older installs or where the consumer unit is at distance from the supply, the MET is a copper bar in the meter cabinet itself with the supply earth terminating directly there.

None of the three is more correct than the others. All are BS 7671 compliant. The choice is normally driven by the original install plus by where the gas plus water services enter the property.

Why MET CSA matters during a board upgrade

One of the most common reasons a consumer unit upgrade quote increases on a survey is the discovery of an undersized main earthing conductor. The MET cable from the supply earth on older installs was sometimes 6mm sq or 10mm sq which was acceptable under earlier editions of the wiring regs. Current BS 7671 requires 16mm sq minimum on a TN-C-S supply for typical UK domestic installs. Where the existing main earthing conductor is undersized, the upgrade work must include replacing it from the meter cabinet to the consumer unit. This is normally the largest single price-add discovered during a board survey.

The same applies to main bonding conductors. Older installs sometimes used 6mm sq main bonding to gas plus water. Current standard is 10mm sq for a TN-C-S supply. Upgrades typically include replacing both bonds back to the MET as part of the new install certification.

Earthing system types: TN-S, TN-C-S, TT

The MET configuration depends on which earthing system the property uses:

  • TN-S. Older system. Earth provided by the cable sheath of the DNO supply. Now uncommon on new installs. Where present the supply earth conductor terminates directly at the MET.
  • TN-C-S (Protective Multiple Earthing, PME). Modern UK default. The DNO supplies a combined earth-neutral conductor which is split locally. The earth side terminates at the MET. Identifiable by a green-yellow conductor between the supply head plus the consumer unit.
  • TT. No earth from the supply. The property has its own earth electrode driven into the ground outside. Mostly found on rural overhead supplies. Requires 30mA RCD protection on every circuit because the earth fault loop impedance is too high for an MCB alone to operate within the disconnection time.
UK regulatory source check. The standards referenced here come from BS 7671:2018+A2:2022 Sections 411 plus 543 (earthing plus protective conductors) plus BS 951 (earthing clamps) published by BSI plus the IET. C-Lec Electrical is a registered installer covering Milton Keynes, Bedford plus the surrounding Bedfordshire area.
How to spot yours

Three signs that
identify your MET

Open your meter cabinet or consumer unit cover. The MET will normally show one of these three identifying features.

Sign 01

The yellow safety label

"SAFETY ELECTRICAL CONNECTION DO NOT REMOVE." A bright yellow durable label directly attached to the terminal or the earthing clamp.

Sign 02

Multiple green-yellow conductors

The MET is the only point where multiple green-yellow protective conductors converge. Earth from supply, CPCs from consumer unit plus main bonding all together.

Sign 03

A copper bar or BS 951 clamp

Either a horizontal copper bar with multiple bolt holes or a brass clamp with the BS 951 marking. Both are designed for permanent multi-conductor termination.

Practical takeaways

Four things every homeowner
should know

Never disconnect anything from the MET

Removing a single conductor from the MET breaks the earthing system. The yellow safety label is mandatory plus serious.

Old MET cables often need replacement

Pre-2008 installs often used 6mm sq or 10mm sq for the main earthing conductor. BS 7671 now demands 16mm sq on most UK domestic installs.

Main bonding terminates here too

The MET is also where the gas plus water main bonds terminate. Loose or missing bonds normally show up at the MET first on an EICR.

TT installs have their own earth rod

If your property is on a TT supply, the MET connects to an earth rod outside. Check the rod is intact plus the BS 951 clamp is sound.

Earthing concerns?

Earthing plus Bonding Upgrades in Milton Keynes

C-Lec Electrical inspects, upgrades plus certifies main earthing terminals plus main bonding conductors to BS 7671 across Milton Keynes, Bedford plus the surrounding Bedfordshire area. Full EIC plus Building Control notification on completion.

For the wider context on consumer units, RCBOs, AFDDs plus the regulations behind UK distribution boards, head back to our full guide to consumer units where every common question is answered in one place.

Part of the hub

Back to the Consumer Units Guide

This article sits inside our complete Consumer Units knowledge base. The hub covers everything from board types plus RCBOs through to landlord requirements plus BS 7671 wiring regulations.

Keep reading

More on consumer
unit anatomy

To understand the bonding conductors that terminate at the MET in detail, head to what is bonding in electrical systems for the practical breakdown of main plus supplementary bonding. To understand the BS 7671 framework that drives the earthing requirements, see consumer unit wiring regulations. To understand the protective devices that depend on a sound MET to function, see what is an RCBO board. If you need an earthing or bonding upgrade in Milton Keynes or Bedford, our consumer unit upgrades service page is the fastest route to a quote.

Frequently asked

MET questions

Where exactly is the MET in my house?
On most UK domestic installs the MET is the earth bar at the base of the consumer unit. On some older installs the MET is a separate copper bar in the meter cabinet. The defining sign is the durable yellow label "SAFETY ELECTRICAL CONNECTION DO NOT REMOVE" attached to the terminal, plus the convergence of multiple green-yellow conductors at one point. Both the consumer unit earth bar plus a separate copper bar with this label are valid MET configurations.
Why does my electrician want to upgrade the main earthing cable?
BS 7671 requires a minimum cross-sectional area of 16mm sq for the main earthing conductor on most UK domestic installs with a TN-C-S (PME) supply. Older installs often used 6mm sq or 10mm sq which was compliant at the time but no longer meets the current standard. When a consumer unit is replaced the entire installation must meet current BS 7671 which means the main earthing conductor needs upgrading too. This is one of the most common scope additions discovered during a board survey.
What happens if the MET connection fails?
A loose or broken MET connection breaks the earthing system. Practically this means an earth fault on any circuit cannot return to the supply earth which prevents the upstream MCB from tripping. The fault current can also raise the metalwork in the property to mains potential which is a serious shock hazard. RCDs may still operate because they detect the residual current rather than relying on the earth path itself. EICR engineers test MET integrity by measuring earth fault loop impedance from accessible earth points. Any reading above the limits in BS 7671 is coded C1 or C2.
Does my MET need a separate earth rod?
Only on a TT supply. If your property has a TN-S or TN-C-S (PME) supply the earth comes from the DNO so no local earth rod is required. The MET on those systems connects to the supply earth at the meter cabinet. On a TT supply (typical of rural overhead supplies) there is no earth from the DNO so the property must have its own earth rod driven into the ground. The conductor from the rod terminates at the MET via a BS 951 earthing clamp.
Can I add a new conductor to the MET myself?
No. Any work on the MET is notifiable under Part P of the Building Regulations. The MET is the most safety-critical termination in the entire installation. A loose, undersized or incorrectly torqued connection can leave the whole property at risk during an earth fault. All work on the MET, the main earthing conductor or main bonding must be carried out by a registered electrician who can issue an EIC plus a Building Control notice. The certificate confirms the conductor sizing, termination plus continuity have all been tested plus meet BS 7671.